B type residual current circuit breakers
Home Products Building Protection DeviceCircuit BreakersB type residual current circuit breakers
B type residual current circuit breakers
B type residual current circuit breaker (earth leakage protection)
The B type residual current circuit breakers provide:
Protection in the event of a continuous fault current on three-phase networks generated by:
- Controllers and variable speed drives
- Battery chargers and inverters
- Backed-up power supplies
They include and also guarantee protection against fault currents:
- Sinusoidal AC residual currents (AC type)
- Pulsed DC residual currents (A type)
Applications requiring 'B' types include:
EV & PV installations
Frequency converters
UPS installations
High-frequency power converters
Building site power supply cabinets
| According to IEC 60947 | ||
| Insulation voltage (Ui) | 400 V | |
| Pollution degree | 3 | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Making and breaking capacity (Im/IDm) | 25/40 A | 500 A |
| 63/80 A | 800 A | |
| 100 A | 1000 A | |
| Surge current withstand (8/20 μs) without tripping | No selective | 250 Â |
| Selective | 3 k | |
| Conditional rated short circuit current (Inc/IDc) | 25/40 A with FU 80 A gG fuse 63 A with FU 100 A gG fuse | 10,000 A 10,000 A |
| 80/100 A with FU 100 A gG fuse | 10,000 A | |
| Degree of protection | Device only | IP20 |
| IP40 with screw shield | ||
| Device in modular enclosure | IP40 | |
| Insulation classe II | ||
| Endurance (O-C) | Electrical | > 2 000 cycles |
| Mechanical | > 5 000 cycles | |
| Operating temperature | -25°C to 40°C | |
| Storage temperature | -40°C to 85°C | |
Model Selection:
| Rated Current | Pole | Model | |||
| (A) | 30mA | 100mA | 300mA | 500mA | |
| 25 | 2 | GDR22530B | GDR225100B | GDR225300B | GDR225500B |
| 40 | 2 | GDR24030B | GDR240100B | GDR240300B | GDR240500B |
| 63 | 2 | GDR26330B | GDR263100B | GDR263300B | GDR263500B |
| 25 | 4 | GDR42530B | GDR425100B | GDR425300B | GDR425500B |
| 40 | 4 | GDR44030B | GDR440100B | GDR440300B | GDR440500B |
| 63 | 4 | GDR46330B | GDR463100B | GDR463300B | GDR463500B |
Protection for EV charging | EV B type earth leakage protection | B type RCD/RCCB/ELCB for EV | EV charging RCCB

Need more information?
Contact us to request pricing, availability and customization options.

Relay for RCCB and RCBO
2ohm and 35ohm relay for rccb circuit breakers

6RCB Electronic and Magnetic type RCBO
Electronic type and magnetic type 2P, 4 pole RCBO, 6-40A, A/AC type

4CB Miniature circuit breakers
3kA, 4.5kA MCB, 6A to 63A, B/C/D type.

8CB 10kA MCB
10kA MCB, 6A to 100A, B/C/D type