The LW26 sereies rotary switch mainly applies to 440V and below,AC 50Hz or 240V and below DC circuits.For breaking and closing,change-over of circuits under unfrequenly manual operation.And the typical application are:control switch of 3 phase motors,control switch gear,control switch of instruments,and change-over switch of machinery and welding machine.

Description
LW26-10
LW26-20
LW26-25
LW26-32
LW26-63
LW26-125
LW26-160
Rated insolation voltage Ui V
660
660
660
660
660
660
660
Rated thermal current
Ith A
10
20
25
32
63
125
160
Rated working voltage
Ue V 240 440 24 110 240 440 24 110 240 440 240 440 240 440 240 440 240 440
Rated working current
Ie 20 20
AC-21A AC-22A
A 10 10 25 25 32 32 63 63 100 100 150 150
AC-23A
A 7.5 7.5 15 15 22 22 30 30 57 57 90 90 135 135
AC-2
A 7.5 7.5 15 15 22 22 30 30 57 57 90 90 135 135
AC-3
A 5.5 5.5 11 11 15 15 22 22 36 36 75 75 95 95
AC-4
A 1.75 1.75 3.5 3.5 6.5 6.5 11 11 15 15 30 30 55 55
AC-15
A 2.5 2.5 5 4 8 5 14 6
AC-13
A 12 0.4 0.4 20 0.5 0.5
power
P
AC-23A
KW 1.8 3 3.7/2.5 7.5/3.7 5.5/3 11/5.5 7.5/4 15/7.5 15/10 30/18.5 30/15 45/22 37/22 75/37
AC-2
KW 2.5 3.7 4 7.5 5.5 11 7.5 15 18.5 30 30 45 37 55
AC-3
KW 1.5 2.2 3/2.2 5.5/3 4/3 7.5/3.7 5.5/4 11/5.5 11/6 18.5/11 15/7.5 30/13 22/11 37/18.5
AC-4
KW 0.37 0.55 0.55/0.75 1.5/1.5 1.5/1.1 3/2.2 2.7/1.5 5.5/3 5.5/2.4 7.5/4 6/3 12/5.5 10/4 15/7.5


Re1: Neutral
Re2: The power under: AC-23A、AC-3、AC-4 are in three phase three pole,and denominator represents the power under single phase two poles.
Mechancal life
Mechanical life without load:0.1×106times,operation frequency is 120 times/h.
Mechanical life with load:0.03×106times operation frequency is 120 times/h.